16621-5
a. Cable transition to VPI Dry Type; Standard (XF HV on left)
b. Distribution class arrestor
c. Current limiting fuse
d. Spare fuses
e. One (1) cable size 500 kcmil Enter at top w/o loop to NEMA drill only
f. Spare fuse holder
g. Run back Bus
3. 500 kVA SST Transformer, Dry (VPI)
a. Primary 4160V
b. Secondary 480Y/277V
c. Copper windings
d. NEMA 1, 150 deg C rise
4. One (1) Spectra Bolt-on AV1 Swb (108A)
a. One service entrance with labeling
b. 3P,4W/480/277V/60Hz; 600A 42kAIC Fully Rated
c. Type 1 enclosure, front access only
d. One group mounted feeder section 35W
e. One Bus bracing 65000 AIC
f. One tapered copper Bus heat rated
g. Dry transformer transition at left end; full height side barriers
5. Service Disconnects
a. One (1) 500A 3 pole SGLA6 (600A Frame)
b. One padlock provision
c. One mechanical copper load lugs
6. Other
a. One fan control power
b. Lifting brackets
c. One Spectra Bolt-on (C/B feeders only) 18X
d. 1 neutral lugs
2.02 TRANSFER SWITCH AND 480V POWER DISTRIBUTION PANEL: The
Contractor will provide a suitable transfer switch in accordance with PIP ELSAP20.
The switch will transfer supply power source from Substation 6A (normal operation
mode) to the 350kW generator (emergency back-up mode). The transfer switch will
feed a 480V distribution panel. The distribution panel will provide 480V power to
MCC5A and the VFD MCC. The transfer switch will have a manual bypass feature.
2.03 350 kW DIESEL GENERATOR: The Contractor will provide a nominal 350kW
skid-mounted diesel generator in accordance with Specification 16201. The diesel
Page view 54